Aprilaire 8800 Manual do Utilizador

Consulte online ou descarregue Manual do Utilizador para Termóestatos Aprilaire 8800. Partner: Aprilaire Model: 8700/8800 Device Type: HVAC Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 6
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 0
Partner: Aprilaire
Model: 8700/8800
Device Type: HVAC
GENERAL INFORMATION
SIMPLWINDOWS NAME:
Aprilaire 64 Zone Control v1.1
CATEGORY:
HVAC
VERSION:
1.1
SUMMARY:
Provides control of all standard functions in all 64 zones.
GENERAL NOTES:
This module will allow control of all standard functions on
all 64 zones of an Aprilaire HVAC system. Parameters that can be set are
heat setpoint, cool setpoint, mode, fan, permanent hold, vacation hold, temporary
hold, and scheduling. True feedback from the Aprilaire will be reflected at the output
of the module. This feedback will also include the current room temperature.
Model 8800 will function as either a thermostat or a humidistat.
The module functions as follow:
1. Select zone to be controlled.
2. Settings for that zone will be requested automatically and reflected at the
output of the module.
3. Make desired zone adjustments
4. Any changes made on the thermostat for the selected zone will be reflected
by the module.
Note:
When the thermostat/humidistat is in Network Override(Hold On) changes made
from the Crestron control system will be ignored.
CRESTRON HARDWARE REQUIRED:
2 or 3-Series Processor.
SETUP OF CRESTRON HARDWARE:
Baud Rate - 9600
Parity - None
Data Bits - 8
Stop Bits - 1
VENDOR FIRMWARE:
N/A
VENDOR SETUP:
Multiple thermostats require Aprilaire Model 8811 RS485 to RS232 protocol adapter,
and Model 8819 Distribution Panel.
Each thermostat needs to be assigned a unique network address from the installer
setup menu. Each thermostat must also have the total number of
thermostats/support modules on the network set installer menu, the number of
nodes must be the same on all thermostats. The system default baud rate is 9600,
however this can be changed to 19,200 in the installer menu.
For model 8800 devices, a selection for thermostat or humidistat must be selected in
the installer menu. The model 8800 default controller type is thermostat.
CABLE DIAGRAM:
Vista de página 0
1 2 3 4 5 6

Resumo do Conteúdo

Página 1 - Device Type: HVAC

Partner: Aprilaire Model: 8700/8800 Device Type: HVAC GENERAL INFORMATION SIMPLWINDOWS NAME: Aprilaire 64 Zone Control v1.1 CATEGORY: HVAC V

Página 2

Partner: Aprilaire Model: 8700/8800 Device Type: HVAC CONTROL: Zone_<1-64> D Pulse to select which zone will be controlled. Hea

Página 3

Partner: Aprilaire Model: 8700/8800 Device Type: HVAC 12. Vacation_Hold_Day S Serial string representing the day of the month for the vacation

Página 4

Partner: Aprilaire Model: 8700/8800 Device Type: HVAC Scheduler_Event_Fan_Mode A Analog signal representing the vacation hold fan mode: 1-Auto

Página 5

Partner: Aprilaire Model: 8700/8800 Device Type: HVAC Mode_Heat_Fb D High to indicate selected zone is in heat mode. Mode_Cool_Fb D High to

Página 6

Partner: Aprilaire Model: 8700/8800 Device Type: HVAC Schedular_Event_Time-Fb S Serial string containing scheduler time for the selected zone.

Comentários a estes Manuais

Sem comentários